Master Control Fire Alarm
CDX Conventional 16591
Industrial UV/IR² Flame Detector
Description :
Unaffected by convection currents, draughts or wind and solar-blind
Tolerant of fumes, vapours, dust and mist
Selectable response speed
Class 1 performance as defined in BS EN54-10:2002 (on the high sensitivity setting)
Solar Blind
Built in auto and manual test
SIL2 Rated
Specification :
Ordering codes : 16591 IFD-MB (Stainless Steel Mounting Bracket)
Operating voltage : 14 - 30 V dc
Alarm Current (selected via by DIL switches) : 9 ~ 28 mA
Test Signal Voltage : 14 to 30 V dc
Current 1.0 A (max)
Relay Contact Ratings Voltage 50 V dc (max)
Power 30 W (max) (resistive loads only)
Power Up Time : 2 seconds (max)
Field of View : 90° min. Cone
Range - Class 1 : 0.1 m2 n-heptane at 25 m
Range - Class 3 : 0.1 m2 n-heptane at 12 m
(see EN54: 10 for sensitivity settings)
Spectral Response : UV (185 – 260 nm) IR (1.0 ~ 2.7 μm)
Operating temperature range : -10 °C to + 55 °C
Storage temperature range : -20 °C to + 65 °C
Maximum humidity : 95% RH - Non condensing (at 40 °C)
Ingress Protection Rating : IP65
Colour / Case Material : Blue / Die-Cast Zinc Alloy (ZA12)
Weight (kg) / Height / Width / Depth (mm : 2 / 142 / 108 / 82